Product detail
Product Introduction
A gas generator is used to generate pressure gas inside the device, and the device is filled with liquid, cooling and environmentally friendly fire inhibitors. The device can be installed in a normal temperature and pressure environment. It starts immediately after receiving the ignition signal from the fire detector. The gas generator quickly builds pressure to push the piston to quickly atomize and release the filled fire extinguishing agent, forming a fire extinguishing agent that meets the requirements.
Fire requires a concentrated aerosol mixture of explosives. In order to achieve the purpose of fire suppression, fire control and fire extinguishing.
The device has the advantages of small size, long life, simple structure, high reliability, independent use, and maintenance-free. Suitable for handling fire environments in small, closed and complex spaces. It is an effective supplement to the pipe network fire protection system. The device can be used in electric bus power lithium battery boxes, energy storage power stations, computer rooms, military system information centers, ship control center computer rooms, automatic
Fire protection in places and areas such as cash machines.
Features
1) Use heptafluoropropane inert gas as the fire extinguishing medium;
2) The battery room fire protection uses a multi-point sensing system to automatically detect temperature and smoke, alarm and start fire extinguishing;
3) The battery room fire protection has three modes: manual control, automatic control and emergency start;
4) The battery room fire protection is equipped with special alarm bells and sound and light alarms;
5) The fire-fighting gas in the battery room meets the fire-extinguishing concentration requirements;
6) The fire controller in the battery room has backup power supply;
7) The battery room fire controller alarm has several node outputs;
8) There will be no burning or explosion of the lithium battery 2 minutes after the fire extinguishing agent injection ends. After the fire extinguishing device ends the injection and continues to suppress it for 10 minutes, the lithium battery should not re-ignite.
Working Principle
After the fire extinguishing device receives the start signal, the gas generator in the device starts. The solid gas generating agent burns to produce a large amount of low-temperature gas to push the piston to drive the liquid fire extinguishing agent to be transported from the valve or pipeline, and is sprayed through the atomizing nozzle to quickly annihilate it. Protected space, carry out extermination fire.
Parameters
serial number | name | parameter |
1 | Operating temperature range | -40℃~+85℃ |
2 | Fire extinguishing agent weight | 2.325kg (±0.015kg) |
3 | Fire extinguishing agent volume | 1.45L(±0.05L) |
4 | Starting device resistance | 2.3±0.5Ω |
5 | electric start signal | 1.2A, duration greater than 50ms |
6 | Electric starting safety current | 0.4A |
7 | Fire extinguishing agent injection time | ≤20s |
8 | Enclosure rating | IP68 |
9 | feedback pressure | 0.6±0.2MPa |
10 | Electrical interface socket model | K282104H-1 |
11 | Device outlet interface | Recommended external thread G3/8 |
Samples
Structures